So how exactly does lightning protection in hydrostatic level sensors work

Many customer wonder why hydrostatic level sensors fail due to lightning strikes, even if they ordered an even sensor with integrated lightning protection. Understanding how the lightning protection works and how lightning strikes affect hydrostatic level sensors is essential in resolving this confusion.
When submersible pressure sensors, a special type of hydrostatic level sensors, were first installed into reservoirs and lakes to monitor level, the sensor would become burned or destroyed following a lightning storm or inclement weather periods. This prompted much research in to the aftereffect of lightning storms on the instrumentation in reservoirs and the cabling to and from the website.
What lightning protection really means
The first thing to comprehend is that the effect of a lightning strike is considerably different based on how near to the pressure sensor the lightning strikes into the ground or installation. It really is fair to say that no level sensor will survive a primary or very close nearby lightning strike, where often the whole cabin including all installed electronics will undoubtedly be incinerated by direct hits.
However, more distant hits will only improve the Voltage differential by for instance 1500 Volts. In case a local lightning strike raises the electric potential of a reservoir, the particular level sensor may provide the shortest method for the raised voltage and current to earth. The energy will then dissipate in to the ground via the level probe and thus destroy or damage its electronics. This may equally be the case when overhead wires take a hit.
So how exactly does lightning protection in level sensors work?
However, Unconventional could be protected from these lightning strikes by installing or integrating a transient voltage protection into the hydrostatic level sensor. As Adequate of short nature of the voltage pulse, a component may be fitted to or built-into the sensor that acts on rising differences in voltage potential. If the voltage goes above say 50 Volts, this lightning protection can short-circuit the electronic circuit to ground, allowing a path to ground for the surge and protecting the electronics around the maximum specified voltage potential.
The component would normally operate in a non-conductive state, but will be conductive for a voltage transient, allowing the voltage spike to flow harmlessly to ground. If the bond to earth isn’t good enough or no lightning protection is integrated within the hydrostatic level sensor, then your electronics will take the entire quantity of energy of the voltage pulse and fail.Which means protection is only as good as the earth grounding supplied by the user.
In outdoor applications, where submersible pressure transmitters are commonly used, WIKA provides an optionally integrated lightning protection inside the level sensors. The sensor electronics will be protected from local power surges and transient high voltage. Lightning protection is really a mix of protection within the instrument and an excellent low impedance earth grounding.
Have a look at the profiles of WIKAs submersible pressure transmitters LH-20 and LH-10.
Please use our contact form if you need further assistance.
Please find further information on this topic on our information platform ?Hydrostatic level measurement?

Leave a Comment